Disertación de Maestría
DOI
https://doi.org/10.11606/D.18.2011.tde-11052011-135603
Documento
Autor
Nombre completo
Guilherme Caetano do Nascimento
Dirección Electrónica
Instituto/Escuela/Facultad
Área de Conocimiento
Fecha de Defensa
Publicación
São Carlos, 2011
Director
Tribunal
Marra Junior, Wiclef Dymurgo (Presidente)
Aguiar, Monica Lopes
Coury, Jose Renato
Título en portugués
Avaliação da qualidade do ar em ambientes internos: biblioteca pública
Palabras clave en portugués
Ambientes internos
Bibliotecas públicas
Qualidade do ar
Resumen en portugués
Ao longo de quinze meses, foram monitorados na Biblioteca Pública Amadeu Amaral, da cidade de São Carlos, SP, os níveis de temperatura, umidade relativa, ruído, intensidade luminosa, contaminação por dióxido de carbono, material particulado total (MPT) e suas frações respiráveis (MP1, MP2,5, MP7 e MP10), avaliação da taxa de ventilação e ocupação, concentração de bioaerossóis e sua identificação. Além disso, foi aplicado um questionário aos ocupantes do local com o intuito de levantar as principais reclamações e queixas relacionadas à qualidade do ar interior. Os resultados mostraram o desconforto térmico do local em todas as salas monitoradas, altos níveis de ruído proveniente do ambiente externo, inadequações relativas à iluminação do local e necessidade de uma atenção especial à taxa de ocupação do prédio. Durante alguns momentos das medições, os níveis de ruído ultrapassaram a barreira dos 80 dB(A), que é um valor bem acima do recomendado em normas, revelando-se um fator de risco para seus usuários e funcionários. Não foram encontrados problemas relacionados à contaminação biológica do local, analisando a concentração de bactérias e fungos. A taxa de ventilação possui valor adequado para o piso 1 e a concentração de gás carbônico se manteve de acordo com os padrões estabelecidos em normas. As respostas dos questionários confirmam os principais resultados encontrados para a Biblioteca, como os altos níveis de ruído, o desconforto térmico do local e as inadequações da iluminação. As recomendações são pautadas na necessidade de realização de ensaios gravimétricos da concentração de material particulado e o desenvolvimento de estudos específicos para a adoção de medidas mitigadores da poluição sonora e, também, da adequação das salas para o conforto térmico dos ocupantes.
Título en inglés
Indoor air quality investigation: public library
Palabras clave en inglés
Air quality
Indoor air
Public libraries
Resumen en inglés
Over fifteen months, levels of temperature, humidity, noise, light intensity, contamination by carbon dioxide, total suspended particles (TSP) and respirable fractions (PM1, PM2.5, PM7 and PM10) were monitored at the Public Library Amadeu Amaral at São Carlos, SP. Investigation of the ventilation rate and occupancy, concentration of bioaerosols and identification were also performed. In addition, a questionnaire was handed over to the occupants of the site in order to raise the main complaints related to indoor air quality. The results showed the discomfort of the place at all rooms monitored, high levels of noise from the outside environment, inadequacies relating to the site illumination and special attention to the building occupancy. During some measurements, the noise levels exceeded the barrier of 80 dB (A), which is above the recommended standards and proved to be a risk factor for its users and employees. No problems were found related to the site biological contamination, analyzing the concentration of bacteria and fungi. The ventilation rate has adequate value to the first floor and carbon dioxide concentration was maintained in accordance with the standards. The questionnaire responses confirm the main findings to the library, such as high noise levels, thermal discomfort and the illumination problem. The main recommendations are based on the need of gravimetric particulate matter investigation and development of specific studies for the adoption of mitigation measures on noise pollution and also the suitability of the rooms to the thermal comfort of occupants.
 
ADVERTENCIA - La consulta de este documento queda condicionada a la aceptación de las siguientes condiciones de uso:
Este documento es únicamente para usos privados enmarcados en actividades de investigación y docencia. No se autoriza su reproducción con finalidades de lucro. Esta reserva de derechos afecta tanto los datos del documento como a sus contenidos. En la utilización o cita de partes del documento es obligado indicar el nombre de la persona autora.
Fecha de Publicación
2011-05-13
 
ADVERTENCIA: El material descrito abajo se refiere a los trabajos derivados de esta tesis o disertación. El contenido de estos documentos es responsabilidad del autor de la tesis o disertación.
  • ALMEIDA, C. L., et al. MATERIAL PARTICULADO, MICROBIOTA AÉREA E RESISTÊNCIA ANTIMICROBIANA DE STAPHYLOCOCCUS AUREUS EM CIRURGIA ORTOPÉDICA. Revista SOBECC (São Paulo), 2013, vol. 18, p. 45-56.
  • MARRA JUNIOR, W. D., AGUIAR, M. L., e NASCIMENTO, G. C. Avaliação da Qualidade do Ar em Ambientes Internos: Biblioteca Pública. In XVIII Congresso Brasileiro de Engenharia Química, Foz do Iguaçu, 2010. Anais do Congresso Brasileiro de Engenharia Química., 2010.
  • MARRA JUNIOR, W. D., e NASCIMENTO, G. C. Indoor Air Quality Investigation: Public Library. In Environmental Health 2011, Salvador, Brazil, 2011. http://www.environmentalhealthconference.com/., 2011.
Todos los derechos de la tesis/disertación pertenecen a los autores