Análise de metodologias para localização de defeitos em cabos isolados de alta tensão do tipo oil filled (OF).
Mots-clés en portugais
Cabo com papel impregnado
Congelamento
Localização de falhas
Traçador perfluorcarbono
Vazamento de óleo
Resumé en portugais
Duas metodologias que podem ser utilizadas na localização de defeitos em cabos isolados de alta tensão do tipo Oil Filled (OF) foram analisadas. As metodologias descritas têm como princípio a localização de vazamentos de óleo, ou seja, todo defeito seguido de vazamento de óleo poderá ser localizado a partir das mesmas. A primeira metodologia é baseada no congelamento dos cabos OF, com a linha desenergizada, a fim de localizar vazamentos de óleo de cabos OF a partir de 300 litros por mês. A segunda metodologia é baseada na utilização de traços de gás perfluorcarbono Perfluorocarbon Tracer (PFT), através de um sistema montado com equipamentos que permitem realizar a localização de vazamentos de óleo de cabos OF a partir de 100 litros por mês, sem a necessidade de desligamento da linha subterrânea. Esta dissertação propõe algumas melhorias na metodologia do congelamento e apresenta as primeiras experiências de utilização do PFT no Brasil para localização de vazamentos de óleo.
Titre en anglais
Analysis of methodologies for fault location in high voltage insulated cables oil filled (OF) type.
Mots-clés en anglais
Freeze
Leak location
Oil leakage
Paper impregnated cable
Perfluorocarbon tracer
Resumé en anglais
Two methods that can be used to locate faults in Oil Filled (OF) cables were analyzed. The methods described have the principle of oil leak location. All defects followed by oil leakage can be located using the same. The first method is based in OF cables freezing, with the line outage, in order to locate oil leaks from 300 liters per month and above. The second method is based on the use of tracer gas - Perfluorocarbon Tracer (PFT) and devices that allow to perform the location of oil leaks from 100 liters per month, without the need of underground line outage. This paper proposes some improvements for the freezing method and presents the first experiments in Brazil using PFT to locate oil leakage.
 
AVERTISSEMENT - Regarde ce document est soumise à votre acceptation des conditions d'utilisation suivantes:
Ce document est uniquement à des fins privées pour la recherche et l'enseignement. Reproduction à des fins commerciales est interdite. Cette droits couvrent l'ensemble des données sur ce document ainsi que son contenu. Toute utilisation ou de copie de ce document, en totalité ou en partie, doit inclure le nom de l'auteur.
Date de Publication
2014-07-16
 
AVERTISSEMENT: Apprenez ce que sont des œvres dérivées cliquant ici.
Tous droits de la thèse/dissertation appartiennent aux auteurs
CeTI-SC/STI
Bibliothèque Numérique de Thèses et Mémoires de l'USP. Copyright © 2001-2024. Tous droits réservés.