Dissertação de Mestrado
DOI
https://doi.org/10.11606/D.18.2017.tde-24012017-152630
Documento
Autor
Nome completo
João Rodrigo Saldanha
Unidade da USP
Área do Conhecimento
Data de Defesa
Imprenta
São Carlos, 2002
Orientador
Banca examinadora
Di Bernardo, Luiz (Presidente)
Mendes, Carlos Gomes da Nave
Sens, Mauricio Luiz
Título em português
Avaliação do desempenho de uma estação de tratamento de água com sistema de dupla filtração, em escala real
Palavras-chave em português
Dupla filtração
Filtração direta ascendente em areia
Operação de estações de dupla filtração
Tratamento de água para abastecimento
Resumo em português
A tecnologia de tratamento com dupla filtração encontra-se em estágio relativamente elevado de desenvolvimento, porém, ainda são poucos os dados de operação em escala real. Este trabalho teve como objetivo avaliar um sistema de dupla filtração em escala real (ETA2) para tratamento de água, do serviço autônomo de água e esgoto da cidade de São Carlos - SP, que trata água bruta proveniente do Ribeirão do Feijão e é constituída de três unidades de filtração cada uma contendo um filtro ascendente e um descendente. Em uma primeira etapa foram levantadas as medidas das unidades de dupla filtração, caracterizado o material filtrante e avaliadas as condições operacionais da ETA 2. Posteriormente, foi estudada a situação geral da ETA por meio de diversos parâmetros (turbidez, pH, expansão da areia na lavagem, contagem de partículas, de coliformes totais e Escherichia. coli), para verificar os principais problemas. Em seguida, realizou-se uma comparação da ETA2 com uma Instalação Piloto de Dupla Filtração. Este trabalho permitiu concluir principalmente que: i) devido às baixas taxas de filtração de unidades filtrantes da ETA2, excessivas dosagens de coagulante e falta de controle de lavagens, geralmente foi baixa a produção efetiva de água (em torno de 90%); ii) o desempenho, algumas vezes insatisfatório das unidades de filtração ascendente e descendente, deveu-se principalmente à ineficiência da mistura de coagulante na água bruta, falta de areia nos filtros ascendentes e à diferença de granulometria nos filtros descendentes; iii) o desenvolvimento da perda de carga nos filtros ascendentes da ETA2 foi mais acentuado na Instalação Piloto devido à mistura de seus materiais filtrantes.
Título em inglês
Evaluation of the performance of the water treatment station with a double filtration system in real scale
Palavras-chave em inglês
Direct up-flow sand filtration
Drinking water production
Operation of double filtration plants
Two-stages filtration
Resumo em inglês
Water treatment by means of a double filtration system is in a relatively high stage of development, however, there are still few data on real scale operations. The aim of this work was to evaluate a double filtration system in a real scale (ETA2) for the treatment of water, of the autonomous service of water and sewer of the city of São Carlos - SP, which treats water from the Ribeirão do Feijão (name of a local river), and is constituted of three filtration units, each a contain a direct up-flow sand filter, and a rapid filter. In the first stage, the sand of the filters was characterized, and the operational conditions of the ETA2 were evaluated. Next, the general situation of the ETA was studied by means of several parameters (turbidity, pH, expansion of the sand during washing process, counting of particles, total coliforms and Escherichia coli), in a order to detect the main problems. Finally, a confrontation between the ETA2 an a double filtration pilot Plant was carried through. This study made infer that: I) due to the low filtration rates of the ETA2`s filtration units, excessive doses of coagulant and lack of control of the washings, the actual production of water was low (around 90%); ii) the sometimes insufficient performance of the direct up-flow sand filtration and rapid filtration systems was mainly caused by an inefficient mixing of the coagulant with the natural water, lack of sand in direct up-flow filters; iii) the building up of the lossof cargo in the direct up-flow san filtration in filters of the ETA2 was more accentuated than in the Pilot Plant due to the mixture of the filtration materials.
 
AVISO - A consulta a este documento fica condicionada na aceitação das seguintes condições de uso:
Este trabalho é somente para uso privado de atividades de pesquisa e ensino. Não é autorizada sua reprodução para quaisquer fins lucrativos. Esta reserva de direitos abrange a todos os dados do documento bem como seu conteúdo. Na utilização ou citação de partes do documento é obrigatório mencionar nome da pessoa autora do trabalho.
Data de Publicação
2017-01-25
 
AVISO: Saiba o que são os trabalhos decorrentes clicando aqui.
Todos os direitos da tese/dissertação são de seus autores
CeTI-SC/STI
Biblioteca Digital de Teses e Dissertações da USP. Copyright © 2001-2024. Todos os direitos reservados.