Disertación de Maestría
DOI
https://doi.org/10.11606/D.18.2011.tde-29072011-100528
Documento
Autor
Nombre completo
Denis Borg
Instituto/Escuela/Facultad
Área de Conocimiento
Fecha de Defensa
Publicación
São Carlos, 2011
Director
Tribunal
Brandão, Dennis (Presidente)
Flauzino, Rogério Andrade
Melo, Jorge Dantas de
Título en portugués
Implementação de uma rede neural em ambiente foundation fieldbus para computação de vazão simulando um instrumento multivariável
Palabras clave en portugués
Computador de vazão
Delta V TM
Foundation fieldbus
HART
Instrumento multivariável
Medidor de vazão
Placa de orifício
Rede neural artificial
Software sensor
Resumen en portugués
Esta dissertação propõe o desenvolvimento de uma rede neural artificial (RNA) direcionada a ambientes foundation fieldbus para realização do cálculo de vazão em dutos fechados. Para tanto, a metodologia proposta utiliza-se de medidas de pressão, temperatura e pressão diferencial, as quais normalmente estão disponíveis em plantas industriais. A principal motivação do emprego das redes neurais reside no seu baixo custo e simplicidade de implementação, o que possibilita o emprego de apenas blocos fieldbus padrões tornando a metodologia independente do fabricante. Foi utilizada uma rede perceptron multicamadas com algoritmo de treinamento backpropagation de Levenberg-Marquardt. O treinamento foi realizado numa programação elaborada para o software Matlab TM. A arquitetura da rede neural foi determinada por métodos empíricos variando-se o número de neurônios e de camadas neurais até se atingir um erro aceitável na prática. Após esses treinamentos foi desenvolvida uma programação para realizar os cálculos de vazão em um ambiente foundation fieldbus utilizando-se para tanto o software DeltaV TM do fabricante Emerson Process Management. Foram obtidos resultados com erro relativo médio de valor de vazão em torno de 1.43% para um primeiro cenário utilizando uma placa de orifício e ar como fluido, e de 0,073% para um segundo cenário utilizando uma placa de orifício e gás natural como fluido, com relação aos valores obtidos através do instrumento multivariável 3095MV TM do fabricante Rosemount. Os valores de erro encontrados validam o método desenvolvido nessa dissertação.
Palabras clave en inglés
Artificial neural network
DeltaV TM
Flow computer
Flow measurement
Foundation fieldbus
HART
Multivariable instrument
Orifice plate
Software sensor
Resumen en inglés
This dissertation proposes the development of an artificial neural network (ANN) directed to foundation fieldbus environment for calculation of flow in closed ducts. The proposed methodology uses measurements of pressure, temperature and differential pressure, which are usually available in industrial plants. The main motivation of the use of neural networks lies in their low cost and simplicity of implementation, which allows the use of standard fieldbus blocks by just making the method independent of the manufacturer. It was used a multilayer perceptron network with backpropagation training and algorithm from Levenberg-Marquardt. The training was programmed in the software Matlab TM. The architecture of the ANN was determined by empirical methods by varying the number of neurons and neural layers until it reaches an acceptable error. After such trainings, it was developed a program to perform the flow calculations in an foundation fieldbus environment using Emerson Process Management's DeltaV TM software. The results were obtained with an average relative error of flow rate of 1.43% for the first scenario using an orifice plate and air as a process fluid, and 0.073% for a second scenario using an orifice plate and natural gas as the fluid related to the values obtained from Rosemount 3095MV TM multivariable instrument. The values of error found validate the method developed in this dissertation.
 
ADVERTENCIA - La consulta de este documento queda condicionada a la aceptación de las siguientes condiciones de uso:
Este documento es únicamente para usos privados enmarcados en actividades de investigación y docencia. No se autoriza su reproducción con finalidades de lucro. Esta reserva de derechos afecta tanto los datos del documento como a sus contenidos. En la utilización o cita de partes del documento es obligado indicar el nombre de la persona autora.