Master's Dissertation
DOI
https://doi.org/10.11606/D.18.2006.tde-16072006-122259
Document
Author
Full name
Alexandre Paciencia Bernardes
E-mail
Institute/School/College
Knowledge Area
Date of Defense
Published
São Carlos, 2006
Supervisor
Committee
Oleskovicz, Mario (President)
Coury, Denis Vinicius
Freitas Filho, Walmir de
Title in Portuguese
Um esquema completo de proteção diferencial de transformadores para testes em um relé digital
Keywords in Portuguese
ATP
corrente de Inrush
proteção diferencial
relé digital
transformador de corrente
transformador de potência
Abstract in Portuguese
Este trabalho apresenta um procedimento completo de simulação da proteção digital diferencial aplicada a transformadores de potência, visando o emprego deste à avaliação do comportamento de relés comercialmente disponíveis. Foi escolhido o software ATP (Alternative Transients Program) como ferramenta para a simulação de distintas situações sobre um sistema diferencial de proteção aplicado a um transformador de 25 MVA. Dentre as ocorrências evidenciadas, destacam-se: situações de faltas internas, faltas externas, situações de energização e energização com falta interna do transformador, condição de sobreexcitação e de saturação de TC (Transformador de Corrente). Cabe comentar que das simulações a real caracterização sobre o relé em teste, fez-se necessário todo um pré-processamento e análise da informação que será convenientemente abordada e justificada no trabalho apresentado, denotando-se um procedimento comum de teste a ser adotado a esta filosofia de proteção. A metodologia e esquema prático adotado trazem uma contribuição importante para a análise laboratorial de modelagens e simulações aplicadas a relés de proteção presentes no mercado e contribui de maneira substancial para os estudos teóricos de possíveis soluções para limitações eventualmente encontradas
Title in English
A complete model of differential protection of transformers for tests in a digital relay
Keywords in English
ATP
current transformer
differential protection
digital relay
Inrush current
power transformer
Abstract in English
This dissertation presents a complete procedure of simulation of digital differential protection applied to power transformers, focusing on its use to evaluate of the behavior of commercially available relays. Software ATP (Alternative Transients Program) was chosen as a tool for the simulation of distinct situations in a differential protection system applied to a 25 MVA three-phase transformer. Amongst the evidenced occurrences internal and external fault conditions, energization with or without internal fault of a three-phase transformer, overexcitation and CT (Current Transformer) saturation conditions were distinguished. It should be mentioned that from simulations to the characterization the real situations on the relay in test, a pre-processing and analysis of the information were necessary, and will be justified in the present study, denoting a common test procedure to be adopted to this philosophy of protection
 
WARNING - Viewing this document is conditioned on your acceptance of the following terms of use:
This document is only for private use for research and teaching activities. Reproduction for commercial use is forbidden. This rights cover the whole data about this document as well as its contents. Any uses or copies of this document in whole or in part must include the author's name.
Publishing Date
2006-07-27
 
WARNING: Learn what derived works are clicking here.
All rights of the thesis/dissertation are from the authors
CeTI-SC/STI
Digital Library of Theses and Dissertations of USP. Copyright © 2001-2024. All rights reserved.