Thèse de Doctorat
DOI
https://doi.org/10.11606/T.3.2000.tde-24102001-160408
Document
Auteur
Nom complet
Flávio Augusto Sanzovo Fiorelli
Adresse Mail
Unité de l'USP
Domain de Connaissance
Date de Soutenance
Editeur
São Paulo, 2000
Directeur
Jury
Silvares, Otavio de Mattos (Président)
Paiva, Marco Antonio Soares de
Peixoto, Roberto de Aguiar
Tavares, Miriam Rocchi
Zerbine, Euryale Jorge Godoy de Jesus
Titre en portugais
Análise do escoamento de fluidos refrigerantes alternativos ao HCFC22 em tubos capilares adiabáticos.
Mots-clés en portugais
ar condicionado
modelagem
refrigeração
simulação
substituição dos HCFCs
tubos capilares
Resumé en portugais
Este trabalho apresenta os resultados da pesquisa "Análise do Escoamento de Fluidos Refrigerantes Alternativos ao HCFC 22 em Tubos Capilares Adiabáticos", desenvolvida para obtenção do título de Doutor em Engenharia no Departamento de Engenharia Mecânica da EPUSP. Essa pesquisa foi motivada pelas resoluções do Protocolo de Montreal, que prevêem a eliminação gradativa do HCFC 22 e, conseqüentemente, impõem a necessidade da realização de estudos sobre o comportamento de fluidos alternativos ecologicamente aceitáveis nos sistemas de refrigeração e seus componentes. Até o momento, as pesquisas e as referências bibliográficas indicam a utilização de misturas zeotrópicas e quase-azeotrópicas como a melhor alternativa para substituição do HCFC 22. Desta forma, foi realizado um extenso levantamento experimental do escoamento do R-407C (uma mistura zeotrópica) e do R-410A (uma mistura quase-azeotrópica) através de tubos capilares, em uma unidade laboratorial construída para essa finalidade. Esse levantamento, realizado para condições de entrada subresfriada e saturada, caracterizou a influência destes fluidos refrigerantes e dos diversos parâmetros operacionais e geométricos no comportamento do tubo capilar em sistemas de refrigeração. Foram desenvolvidos dois modelos (fases separadas e homogêneo) para a modelagem matemática do escoamento de fluidos refrigerantes através de tubos capilares, a fim de verificar o efeito do tipo de escoamento adotado nessa modelagem. A validação dos programas de simulação desenvolvidos, tanto para os dados experimentais obtidos no presente trabalho quanto para dados de literatura, mostra que os dois modelos podem ser utilizados para essa modelagem, apresentando desvios semelhantes em relação aos dados experimentais. A fim de aprimorar os modelos, é necessária a realização de estudos mais aprofundados sobre o atraso de vaporização e a ocorrência de blocagem na saída do tubo capilar. Por fim, foi realizado um estudo numérico comparativo do desempenho do HCFC 22 e dos alternativos R-407C e R-410A, que indicou que o primeiro é adequado tanto para o "retrofit" de equipamentos existentes quanto para utilização em novos equipamentos, enquanto que o segundo deve ser utilizado apenas em novos equipamentos.
Titre en anglais
Analysis of HCFC 22 alternative refrigerant fluids flow through adiabatic capillary tubes.
Mots-clés en anglais
air conditioning
capillary tubes
HCFC replacement
modelling
refrigeration
simulation
Resumé en anglais
This work presents the results of the research activities on the "Analysis of HCFC 22 Alternatives Flow Through Adiabatic Capillary Tubes", developed at the Mechanical Engineering Department of Escola Politécnica da Universidade de São Paulo. Such research was motivated by the resolutions of Montreal Protocol, which imposes gradational elimination of several refrigerants, among them HCFC 22. This leads to the necessity of carrying out studies on the behaviour of ecologically acceptable refrigerants in refrigeration systems and components. So far, researches and literature indicate the usage of zeotropic and near azeotropic refrigerant mixtures as the best alternative to HCFC 22. Therefore, it was performed an extensive experimental survey on R-407C (a zeotropic mixture) and R-410A (a near azeotropic mixture) flow through capillary tubes. Such survey, which was carried out for both subcooled and two-phase inlet conditions, characterised the influence of these refrigerants, as well as the several operating and geometric parameters on the behaviour of capillary tubes used in refrigeration systems. In order to analyse the effect of different approaches for two-phase flow, it was developed two models (separated flow model and homogeneous model) for mathematical simulation of refrigerant flow through adiabatic capillary tubes. Models validation using both experimental and literature data shows that the two models are suitable for such simulation, with the same error level in relation to experimental data. It was also noticed that it is necessary to perform more comprehensive studies on the delay of vaporisation and capillary tube outlet shocking flow phenomena. Finally, it was performed a comparative study on the performance of HCFC 22, R-407C and R-410A, which indicates that R-407C is suitable both for retrofitting actual equipment and for new ones, while R-410A is suitable only for new equipment.
 
AVERTISSEMENT - Regarde ce document est soumise à votre acceptation des conditions d'utilisation suivantes:
Ce document est uniquement à des fins privées pour la recherche et l'enseignement. Reproduction à des fins commerciales est interdite. Cette droits couvrent l'ensemble des données sur ce document ainsi que son contenu. Toute utilisation ou de copie de ce document, en totalité ou en partie, doit inclure le nom de l'auteur.
Tese.pdf (1.63 Mbytes)
Date de Publication
2003-05-14
 
AVERTISSEMENT: Apprenez ce que sont des œvres dérivées cliquant ici.
Tous droits de la thèse/dissertation appartiennent aux auteurs
CeTI-SC/STI
Bibliothèque Numérique de Thèses et Mémoires de l'USP. Copyright © 2001-2024. Tous droits réservés.