Nombre completo
Geraldo Roberto de Almeida
Dirección Electrónica
Instituto/Escuela/Facultad
Área de Conocimiento
Fecha de Defensa
Publicación
São Paulo, 2011
Director
Tribunal
Zanetta Júnior, Luiz Cera (Presidente)
Bartoli, Julio Roberto
Grimoni, José Aquiles Baesso
Nishimura, Fumitaka
Prata, Alvaro Toubes
Título en portugués
Tecnologia para linhas de transmissão instaladas diretamente enterradas em solos sujeitos a instabilidade térmica e hidrológica: novos materiais para backfill; sistema de controle de temperatura
Palabras clave en portugués
Backfill
Cabos elétricos
Engenharia elétrica
Linhas subterrâneas de energia elétrica
Resumen en portugués
Este trabalho é um conjunto de conhecimentos sistematizado, alguns já disponíveis através da engenharia e/ou da tecnologia, e outros desenvolvidos durante este trabalho para solução de problemas que freqüentemente se apresentam na modalidade de instalação de linhas de transmissão subterrânea enterradas diretamente no solo. Nas linhas de transmissão diretamente enterrada, a corrente máxima circulante nos condutores depende do salto térmico entre o condutor e a temperatura máxima do solo em um ponto remoto onde os cabos estão instalados. Duas variáveis além da corrente teem um papel de extrema relevância: A resistência elétrica do condutor e blindagens que define as perdas joules geradas pelos condutores e capas metálicas, respectivamente e a resistência térmica externa do solo circunstante ao cabo enterrado. A parte devido às perdas joules já foi exaustivamente estudada e sistematização atual é suficiente para a solução da maioria dos problemas de engenharia, mas a parte do conhecimento da resistência térmica externa tem ainda muitos pontos que ainda não foram totalmente esclarecidos: sejam na modelagem, sejam nos materiais sejam no controle da fenomenologia. O escopo deste trabalho é dar uma contribuição no papel da resistência térmica externa aos cabos enterrados através de uma engenharia simultânea (Elétrica, Mecânica e Civil) assistida por tecnologia de desenvolvimento de materiais (Backfill).
Título en inglés
Technology for underground transmission lines direct buried installed in soils with tendency of thermal and hydrological instabilities.
Palabras clave en inglés
Backfill
Electric engineering
Electric cables
Underground transmission lines
Resumen en inglés
The present work is a set of systematized knowledge, some of them available in the engineering and technological literature and others developed during this work to solve problems which presents in direct buried cables modalities. In direct buried transmission lines the current carrying in the conductors depends on the temperature rise of the conductor in respect of the temperature of remote soil. Two variables beyond the electrical current on the conductor play a paramount role: The electrical resistance of the conductor and sheaths which define the Joules losses upon the conductor and sheath and the thermal resistance between cable and soil. The role of Joule losses has been sufficiently studied providing solutions for large class of engineering problems, but the available knowledge regarding external thermal resistivity has several points under considerations yet: Even in modeling, materials and phenomenology control. The scope of this work is to present a short contribution on the role of external thermal resistance between cables and soil through the simultaneous frame work (Electrical, Mechanical and Civil engineering) and Technological development of materials (Backfill).
 
ADVERTENCIA - La consulta de este documento queda condicionada a la aceptación de las siguientes condiciones de uso:
Este documento es únicamente para usos privados enmarcados en actividades de investigación y docencia. No se autoriza su reproducción con finalidades de lucro. Esta reserva de derechos afecta tanto los datos del documento como a sus contenidos. En la utilización o cita de partes del documento es obligado indicar el nombre de la persona autora.
ANEXOS.pdf (2.01 Mbytes)
Fecha de Publicación
2011-12-08
 
ADVERTENCIA: El material descrito abajo se refiere a los trabajos derivados de esta tesis o disertación. El contenido de estos documentos es responsabilidad del autor de la tesis o disertación.
  • ZANETTA JUNIOR, L. C., et al. 70 Years of MV Cables in Brazil, Reliability of: Cables; Splices and Potheads. In Jicable´11, Versailles, 2011. Gicable Procedings Recueil Des Communications., 2011.
  • ZANETTA JUNIOR, L. C., et al. Backfill Replacement Save Underground Transmission Lines Cost and Postpone Investmensts. In Jicable´11, Versailles, 2011. Gicable Procedings Recueil Des Communications., 2011.
  • ZANETTA JUNIOR, L. C., Coelho, Marcio, and ALMEIDA, G. Special Bonding and Earthing of Cables for a 230KV Three Phase System with Four Cables. In Jicable´11, Versailles, 2011. Gicable Procedings Recueil Des Communications., 2011.
Todos los derechos de la tesis/disertación pertenecen a los autores