Mémoire de Maîtrise
DOI
https://doi.org/10.11606/D.3.2018.tde-09042018-145504
Document
Auteur
Nom complet
Rodney Itiki
Unité de l'USP
Domain de Connaissance
Date de Soutenance
Editeur
São Paulo, 2018
Directeur
Jury
Santo, Silvio Giuseppe Di (Président)
Almeida, Madson Cortes de
Flauzino, Rogério Andrade
Titre en portugais
Metodologia para mapeamento de zonas operacionais em sistemas de transmissão VSC-HVDC.
Mots-clés en portugais
Conversores elétricos
Eletrificação
Mineração submarina
Portos
Sistemas elétricos de potência
Transbordo de carga
Usinas nucleares
Resumé en portugais
Sistemas de transmissão de energia elétrica em corrente contínua e alta tensão baseados em tecnologia de conversores a fonte de tensão (VSC-HVDC), ao contrário de linhas de transmissão em corrente alternada, operam como elementos de controle de variáveis elétricas, podendo ser úteis na estabilidade do sistema de potência. Mas apesar desta vantagem, sistemas VSC-HVDC possuem limitações no desempenho estável, o que enseja o desenvolvimento de uma metodologia para mapeamento de suas zonas de operação estável e possíveis regiões de instabilidade. Inicialmente estudou-se os detalhes da tecnologia VSC-HVDC tais como o funcionamento da eletrônica de potência e estratégias de controle utilizadas. Em seguida, investigou-se os modelos de geradores síncronos para interconexão com o lado CA das estações conversoras do VSC-HVDC. E, finalmente, aplicou-se a tecnologia VSC-HVDC sobre um modelo de sistema de potência com uma estação conversora localizada em um porto offshore e uma outra no continente, próxima à rede de alta tensão em corrente alternada. Simulações e análise deste sistema foram executadas considerando várias condições operacionais. O gráfico de potência gerada e consumida, obtido pela aplicação da metodologia, apresenta grande potencial de uso prático como por exemplo sua implementação na interface homem-máquina da estação de operação do porto offshore, provendo informação em tempo real de alto nível ao operador do sistema elétrico do porto offshore e consequentemente aumentando sua consciência situacional quanto a proximidade dos limites de instabilidade.
Titre en anglais
Methodology for mapping operational zones in VSC-HVDC transmission sytems.
Mots-clés en anglais
Electrical engineering
Electrification
Engineering
Floating nuclear power plant
Offshore ports
Power ships
PSCAD
Subsea mining
Transshipment
VSC-HVDC
Resumé en anglais
High voltage direct current power transmission systems based on voltage source converters (VSC-HVDC), as opposed to alternating current ones, operates as elements of control of electrical variables, being useful for stability of power system. Besides this advantage, VSC-HVDC systems have limitations in stable performance, which instigates the development of a methodology for mapping its operational zones of stability and possible regions of instability. The author initially studied the details of the VSC-HVDC technology such as the power electronic principles and the control strategies used on this research. Subsequently, the author investigated synchronous generator models for interconnection on the AC side of the VSC-HVDC converter stations. Finally, the author applied the VSC-HVDC technology on a model of power system with two converter stations, one located on an offshore port and the other on the shore, next to an alternating current high voltage power grid. Simulations and analysis of this system were carried out considering various operational conditions. The graphic of generated and consumed power on offshore port, obtained by the application of the methodology for mapping operational zones, presents a great potential of being implemented in the man-machine interface of an operation workstation, thus providing high level online information for the operator of the offshore port electrical system and consequently improving its situational awareness of the proximity to instability limits.
 
AVERTISSEMENT - Regarde ce document est soumise à votre acceptation des conditions d'utilisation suivantes:
Ce document est uniquement à des fins privées pour la recherche et l'enseignement. Reproduction à des fins commerciales est interdite. Cette droits couvrent l'ensemble des données sur ce document ainsi que son contenu. Toute utilisation ou de copie de ce document, en totalité ou en partie, doit inclure le nom de l'auteur.
RodneyItikiOrig17.pdf (8.90 Mbytes)
Date de Publication
2018-04-09
 
AVERTISSEMENT: Apprenez ce que sont des œvres dérivées cliquant ici.
Tous droits de la thèse/dissertation appartiennent aux auteurs
CeTI-SC/STI
Bibliothèque Numérique de Thèses et Mémoires de l'USP. Copyright © 2001-2024. Tous droits réservés.