Titre en portugais
Métodos de avaliação de contribuição de harmônicos por correlação e análise fasorial.
Mots-clés en portugais
Qualidade de energia elétrica
Transmissão de energia elétrica
Resumé en portugais
Este trabalho apresenta uma metodologia de tratamento e análise baseada em medições de tensões e correntes com conteúdo harmônico para avaliar a contribuição de harmônicos dos elementos da rede elétrica baseando-se somente nas medições sincronizadas de alguns pontos da rede. Os métodos de análise propostos neste trabalho consistem em análises por correlação entre as correntes harmônicas de dois locais diferentes, utilizando os registros semanais de valores eficazes das correntes harmônicas medidas, buscando identificar as linhas de transmissão que possuem o mesmo comportamento de correntes harmônicas quanto a sua variação semanal em amplitude e em análises de fasores medidos nestes locais para determinar os fluxos de correntes sobre as barras do sistema. Para demonstrar o método, é apresentado um estudo de caso de uma campanha de medição feita pelo Operador Nacional do Sistema e pela Universidade de São Paulo, nos anos de 2007 e 2008, sobre as correntes de 5ª harmônica que sobrecarregavam os filtros na Subestação de Ibiúna. O método foi utilizado para investigar as origens dessas correntes no sistema de alta tensão. Os resultados da análise por correlação indicaram as linhas de transmissão com maior contribuição para as correntes absorvidas pelos filtros. Essas correntes são originárias de duas subestações e foi possível detectar a influência dos cabos subterrâneos ligados a estas subestações na amplificação destas correntes. Análises fasoriais nas subestações ao longo dos corredores estudados serviram para validar os resultados obtidos da análise por correlação e uma simulação do fenômeno de ressonância harmônica foi realizada, confirmando a suspeita de amplificação das correntes de 5ª harmônica nos cabos subterrâneos.
Titre en anglais
Methods to evaluate harmonics contribution by correlation and phasor analysis.
Mots-clés en anglais
Power quality
Power transmission
Resumé en anglais
This MSc thesis presents a methodology of treatment and analysis based on measurements of harmonic voltage and current to evaluate the harmonic contribution of the network elements in power systems based only on synchronized measurements of few points in the network. The method consists in a correlation analysis of weekly recordings of RMS values of harmonic currents measurements, to identify power lines that present the same behavior in harmonic currents regarding their weekly variation in amplitude. Another approach performs a phasor analysis of currents measured to determine current flows incoming some specific network buses. In order to demonstrate the method, a case study is considered, which consists in a measurement campaign carried out by the ISO and the University of São Paulo, in the years of 2007 and 2008, on the pattern of 5th harmonic currents that overload the filters installed at the Ibiúna Substation. The method was used to investigate the origins of these currents at the high voltage system. The outcome of the correlation analysis indicated the transmission lines with greater contribution to the currents absorbed by the filters. These currents originate from two substations and it was also detected the influence of underground cables connected to these substations in the amplification of these currents. Phasor analysis in substations applied to the studied power lines validated the results obtained from correlation analysis and a simulation of the phenomenon of harmonic resonance was performed, bringing confirmation of the amplification of the 5th harmonic current on the underground cables.
 
AVERTISSEMENT - Regarde ce document est soumise à votre acceptation des conditions d'utilisation suivantes:
Ce document est uniquement à des fins privées pour la recherche et l'enseignement. Reproduction à des fins commerciales est interdite. Cette droits couvrent l'ensemble des données sur ce document ainsi que son contenu. Toute utilisation ou de copie de ce document, en totalité ou en partie, doit inclure le nom de l'auteur.
Date de Publication
2011-09-12
 
AVERTISSEMENT: Apprenez ce que sont des œvres dérivées cliquant ici.
Tous droits de la thèse/dissertation appartiennent aux auteurs
CeTI-SC/STI
Bibliothèque Numérique de Thèses et Mémoires de l'USP. Copyright © 2001-2024. Tous droits réservés.