Master's Dissertation
DOI
https://doi.org/10.11606/D.3.2008.tde-07102008-110310
Document
Author
Full name
Thais Aya Hassan Inatomi
E-mail
Institute/School/College
Knowledge Area
Date of Defense
Published
São Paulo, 2008
Supervisor
Committee
Leite, Brenda Chaves Coelho (President)
Cheng, Liang Yee
Lamberts, Roberto
Title in Portuguese
Análise da eficiência energética do sistema de condicionamento de ar com distribuição pelo piso em ambiente de escritório, na cidade de São Paulo, utilizando o modelo computacional Energyplus.
Keywords in Portuguese
Distribuição de ar pelo piso
Programa Energyplus
Simulação energética
Sistemas de refrigeração e ar condicionado
Abstract in Portuguese
Este trabalho tem por finalidade avaliar o desempenho energético do sistema de condicionamento de ar com distribuição pelo piso (Underfloor Air Distribution System UFAD) em ambientes de escritório, considerando diferentes possibilidades de arquitetura do sistema e seus modos de operação com ciclos economizadores. Por meio de simulação computacional, as avaliações foram realizadas para o clima da cidade de São Paulo ao longo de um ano metereológico típico, mantendo as condições de conforto térmico no ambiente. O programa de simulação selecionado como ferramenta foi o EnergyPlus 2.1.0.023, visto que modelos numéricos nele implementados representam adequadamente o sistema UFAD e os ciclos economizadores. Como referência para o desenvolvimento dos modelos de simulação foi utilizada uma câmara de testes representativa de um ambiente de escritórios. Esta câmara foi desenvolvida por Leite (2003) para avaliação do conforto térmico propiciado pelo sistema UFAD. As curvas de distribuição de temperatura resultantes das simulações foram similares às curvas resultantes das medições executadas por esta autora. As simulações foram realizadas para duas arquiteturas diferentes do circuito de ar (com e sem desvio do ar de retorno) combinados com três diferentes modos de operação relacionados à vazão do ar exterior. A análise dos dados climáticos da cidade de São Paulo demonstra que a tomada de ar exterior pode ser majorada com a utilização de ciclos economizadores, reduzindo o consumo de energia do sistema. Os resultados desta pesquisa indicam uma estreita relação entre arquitetura do sistema, controle dos ciclos economizadores, e dados climáticos, revelando que a combinação entre esses parâmetros pode reduzir em 34,5% o consumo de energia elétrica do sistema UFAD na cidade de São Paulo.
Title in English
Energy efficiency analysis of underfloor air distribution (ufad) system for office rooms, at São Paulo city, using the ENERGYPLUS software.
Keywords in English
Economizer cycles
Energy building simulation
Heating
Underfloor air distribution
Ventilating air conditiong (HVAC) system
Abstract in English
The purpose of this research is to evaluate the energy performance of the Underfloor Air Distribution (UFAD) system at office buildings, considering different air loops design and economizer cycles while keeping thermal comfort for the weather data of São Paulo city, Brazil. Simulations were held using the EnergyPlus software version 2.1.0.023, since its numerical models can well represent UFAD systems and economizer cycles. One chamber representing an office room was used as reference for the simulation models. This chamber was developed by Leite (2003) to evaluate the thermal comfort conditions provided by the UFAD system. The curves of temperature distribution obtained from simulation were similar to those experimentally obtained by Leite (2003). Simulations were performed for two different air loops (with and without return air bypass) combined with three different outside air controls. The São Paulo weather data analysis demonstrates that the outside air flow can be increased with the use of economizer cycles, reducing electric energy consumption of the UFAD system. The results of this research indicate that there is a tight relationship between the system air loop design, economizer cycle control and weather data, which reveals that the combination between these parameters can reduce about 34,5% the electric energy consumption of UFAD system at São Paulo city.
 
WARNING - Viewing this document is conditioned on your acceptance of the following terms of use:
This document is only for private use for research and teaching activities. Reproduction for commercial use is forbidden. This rights cover the whole data about this document as well as its contents. Any uses or copies of this document in whole or in part must include the author's name.