• JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
 
  Bookmark and Share
 
 
Doctoral Thesis
DOI
https://doi.org/10.11606/T.3.2004.tde-29092004-145949
Document
Author
Full name
Laerte Bernardes Arruda
E-mail
Institute/School/College
Knowledge Area
Date of Defense
Published
São Paulo, 2004
Supervisor
Committee
Prado, Racine Tadeu Araujo (President)
Goncalves, Orestes Marraccini
Ilha, Marina Sangoi de Oliveira
Porto, Rodrigo de Melo
Simões-Moreira, José Roberto
Title in Portuguese
Operação de sistemas de aquecimento solar de água com controle de vazões em coletores planos.
Keywords in Portuguese
aquecimento solar de água
automação predial
sistemas prediais
Abstract in Portuguese
O presente trabalho consiste em um estudo experimental sobre o efeito do controle de vazões em sistemas de aquecimento solar de água em instalações com grande número de coletores, onde o gradiente de temperatura não é suficiente para circular a água por termossifonagem. Foi avaliado o desempenho de todo o sistema sob diferentes condições de insolação, de vazão, de diferenciais de temperatura entre os coletores e o reservatório, em regime não permanente. Os resultados experimentais foram comparados com a equação de rendimento dos coletores, para condições de regime quase permanente, obtida segundo a norma da ABNT - NBR 10184/1988. Os ensaios foram realizados em duas baterias de testes, cada uma composta de dois coletores industrializados e um reservatório isolado termicamente. Em uma destas baterias, o fluxo de água entre os coletores e o reservatório ocorreu por termossifonagem, isto é, sem nenhuma restrição à vazão; na outra bateria, a vazão foi controlada por um registro e uma bomba hidráulica. Um sistema de automação coletou e processou os dados de forma a permitir a execução dos controles desejados, inclusive a simulação de consumo de água quente. O sistema com circulação natural, isto é, por termossifão, demonstrou ter uma grande habilidade de se adaptar à disponibilidade de energia com as temperaturas da água armazenada, por meio da otimização da velocidade da troca de calor. Foi desenvolvido, tomado como referência o escoamento por termossifão, um modelo de operação para sistemas diretos ativos que calcula a vazão com base no monitoramento das temperaturas das extremidades das tubulações que interligam o reservatório e os coletores, temperatura do ar, radiação solar disponível e vazão no instante anterior. O modelo foi testado experimentalmente e a operação do sistema ativo resultou em significativa melhora a eficiência.
Title in English
Operation of solar water-heating systems with flow control on flat plate collectors.
Keywords in English
building automation
building systems
solar water-heating
Abstract in English
The focus of this work is the experimental study of the effect of water control discharge in solar water-heating systems with a large number of collectors where the temperature gradient is not sufficient for thermosiphon water circulation. The performance of the system was evaluated under different conditions of solar radiation, flow rate, temperature differential between solar collectors and the storage tank and under transient conditions. The results were compared to a collector's performance equation of the quasi-steady-state model according to ABNT-NBR 10184/1988 standard. The tests were carried out on two systems each one constituted of two manufacturing collectors and one thermal tank. In one of these systems the flow between the collectors and storage occurred by thermosiphoning, i.e., by natural convection and without discharge restrictions. In the other, the flow control was done by means of a valve and a pump. In order to allow the execution of the desired controls, including hot water consumption, data were colleted and controlled through an automation system. The system of natural circulation shows a great ability to adaptation of disposal energy with water temperature stored, through velocity of heat exchange optimization. An operation model was developed, having thermosiphoning water circulation as reference, for active direct circulation systems that calculate the discharge taking into consideration the monitoring of the differential temperature between solar collectors and the storage tank, the air temperature, solar radiation available and the flow rate on previous time interval. This model was experimentally tested and resulted in a significant improvement in performance of the system operation.
 
WARNING - Viewing this document is conditioned on your acceptance of the following terms of use:
This document is only for private use for research and teaching activities. Reproduction for commercial use is forbidden. This rights cover the whole data about this document as well as its contents. Any uses or copies of this document in whole or in part must include the author's name.
Publishing Date
2004-10-04
 
WARNING: Learn what derived works are clicking here.
All rights of the thesis/dissertation are from the authors
CeTI-SC/STI
Digital Library of Theses and Dissertations of USP. Copyright © 2001-2024. All rights reserved.