• JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
 
  Bookmark and Share
 
 
Disertación de Maestría
DOI
https://doi.org/10.11606/D.3.2010.tde-16082010-145800
Documento
Autor
Nombre completo
Thiago Forteza de Oliveira
Dirección Electrónica
Instituto/Escuela/Facultad
Área de Conocimiento
Fecha de Defensa
Publicación
São Paulo, 2010
Director
Tribunal
Mierzwa, José Carlos (Presidente)
Mendes, Carlos Gomes da Nave
Teixeira, Antonio Carlos Silva Costa
Título en portugués
Tratamento de água para abastecimento público por sistema de separação por membrana de ultrafiltração: estudo de caso na ETA Alto da Boa Vista (São Paulo, SP).
Palabras clave en portugués
Processos de separação por membranas
Tratamento de água
Ultrafiltração
Resumen en portugués
Os processos de separação por membranas, especialmente a microfiltração e a ultrafiltração, são tecnologias emergentes para o tratamento de águas de abastecimento pela possibilidade de obtenção de águas com melhor qualidade em estações de tratamento mais compactas, de fácil automação, com menor geração de lodo e custo competitivo em relação ao sistema convencional de tratamento. A presente pesquisa avaliou o desempenho do processo de ultrafiltração no tratamento de água na ETA Alto da Boa Vista, que se utiliza do processo convencional tratando água do Reservatório Guarapiranga, manancial degradado da Região Metropolitana de São Paulo, sob os pontos de vista do desempenho operacional de produção de água e remoção de contaminantes. Tendo como água bruta, a água decantada da ETA ABV, o sistema operou por 2995 horas e 40 minutos, de agosto de 2009 a janeiro de 2010, produzindo com fluxo médio normalizado de 24,3 ± 2,2 L.h-1.m-2, pressão transmembrana de 94,2 ± 6,6 kPa e recuperação de 90,6 ± 0,9%. Foram analisados 13 pares de amostras de alimentação e permeado que indicaram a rejeição de COT de 11,2±8,6% (permeado=2,18±0,20 mg.L-1) , cor aparente 57,5±15,4% (permeado=2±2 mg.L-1 Pt- Co), condutividade elétrica 2,2±1,3% (permeado=138,2±17,8 S.cm-1), turbidez 92,7±4,5% (permeado=0,040±0,010 uT) e substâncias com absorção de radiação UV em 254nm 19,7±8,2% (permeado=0,025±0,008 cm-1). Em uma única amostra analisada, a rejeição a coliformes totais foi de 100%. Não foram detectados coliformes termotolerantes. Em 22/01/2010 foram coletadas amostras de alimentação e permeado para análise segundo Portaria 518 do Ministério da Saúde que indicou rejeição da contagem de bactérias heterotróficas de 98,98%, fluoretos de 36,49%, trihalometanos totais de 30,91%, alumínio total de 100%, cloretos de 20,29%, manganês total de 14,29% e sódio total de 0,81%. Em comparação com a água de abastecimento produzida na ETA ABV, a água do permeado da ultrafiltração apresentou qualidade melhor especialmente em relação à turbidez.
Título en inglés
Drinking water treatment by ultrafiltration: case study at Alto da Boa Vista WTP(São Paulo- SP).
Palabras clave en inglés
Membrane separation processes
Ultrafiltration
Water treatment
Resumen en inglés
Membrane processes, specially microfiltration and ultrafiltration, are emerging technologies for drinking water treatment due the possibility for producing high quality water through compact treatment plants that are easier to automate with reduced sludge production and cost competitive compared with conventional processes. In this research it had been evaluated the ultrafiltration performance for water treatment at Alto da Boa Vista Water Treatment Plant that runs with conventional process, in São Paulo Metropolitan Region, from the viewpoints of water production and contaminants removal. An UF pilot plant was operated during 2995 hours and 40 minutes from August 2009 to January 2010 treating water from sedimentation tanks outlet. The UF pilot plant was able to operate with normalized flux of 24,3 ± 2,2 L.h- 1.m-2, transmembrane pressure of 94,2 ± 6,6 kPa and water recovery of 90,6 ± 0,9%. A total of 13 pairs of samples from feed and permeate were analyzed. The results were TOC rejection of 11,2±8,6% (permeate=2,18±0,20 mg.L-1), apparent color of 57,5±15,4% (permeate=2±2 mg.L-1 Pt-Co), conductivity of 2,2±1,3% (permeate=138,2±17,8 S.cm-1), turbidity 92,7±4,5% (permeate=0,040±0,01 uT) and UV 254nm 19,7±8,2% (permeate=0,025±0,008 cm-1). In an unique sample analysed for total coliforms, the rejection was 100%. Faecal coliforms were not detected in this sample. A sample of feed and permeate was collected at 01/22/2010 for analyses according to Portaria 518 (Brazilian drinking water regulations) that resulted in heterotrophic bacteria rejection of 98,98%, fluoride of 36,49%, total THM of 30,91%, total aluminium of 100%, chloride of 20,29%, total manganese of 14,29% and total sodium of 0,81%. In comparison with drinking water produced at Alto da Boa Vista WTP, the permeate of UF pilot plant was better in quality specially in terms of turbidity.
 
ADVERTENCIA - La consulta de este documento queda condicionada a la aceptación de las siguientes condiciones de uso:
Este documento es únicamente para usos privados enmarcados en actividades de investigación y docencia. No se autoriza su reproducción con finalidades de lucro. Esta reserva de derechos afecta tanto los datos del documento como a sus contenidos. En la utilización o cita de partes del documento es obligado indicar el nombre de la persona autora.
Fecha de Publicación
2010-09-15
 
ADVERTENCIA: Aprenda que son los trabajos derivados haciendo clic aquí.
Todos los derechos de la tesis/disertación pertenecen a los autores
CeTI-SC/STI
Biblioteca Digital de Tesis y Disertaciones de la USP. Copyright © 2001-2024. Todos los derechos reservados.